MOXA ioLogik E2242

SPHINX in Europe
DE
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Product groups > I/O Modules > MOXA ioLogik E2242

MOXA ioLogik E2242

Smart Ethernet remote I/O with Click&Go, 4 AIs, and 12 DIOs

MOXA ioLogik E2242
4251_12599.png
4251_8585.png
  • PropertiesProperties
  • DescriptionDescription
  • Further InformationFurther Information
  • PDFPDF
  • Active communication with patented MX-AOPC UA Server and Active OPC server
  • Smart alarm management with email, SNMP traps, TCP, UDP
  • Save time and wiring costs with peer-to-peer communication
  • Front-end intelligence with patented Click&Go control logic, up to 24 rules
  • Simplify I/O management with MXIO library for Windows or Linux
  • Web browser configurations over HTTP
  • Supports SNMP v1/2c/3
  • Wide operating temperature range of -40 to 75°C (-40 to 167°F)
Moxa’s ioLogik E2200 is a new type of Ethernet micro RTU controller, which is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa’s ioLogik E2200 series with Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Ethernet micro RTU controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.

Actice Alarming with Local Intelligence
The ioLogik E2200 Micro RTU supports simple and powerful Click&Go™ technology to deliver event-driven reports and allow alarm messages to be sent by email, TCP/UDP, and SMNP Trap with real-time stamps. With built-in Click&Go™ intelligence, the ioLogik E2200 micro RTU can be used for simple output control when it is triggered by input status, without the need for a PC controller. The ioLogik E2200 micro RTU reports I/O status automatically based on user-specified conditions. This report by-exception approach requires far less bandwidth than the traditional polling approach.

ProdGrafik

ioLogik E2242 Specifications


  • Inputs and Outputs

    Analog Inputs
    4 channels

    Configurable
    DI/Os 12 channels


  • Analog Input

    Type
    Differential input

    Resolution
    16 bits

    I/O Mode
    Voltage / Current

    Input Range
    ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA

    Accuracy
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 and 60°C
    ±0.5% FSR @ -40 and 75°C

    Sampling Rate
    All channels: 32 samples/sec
    Per channel: 8 samples/sec
    Single channel: 100 samples/sec

    Input Impedance
    200k ohms (min.)

    Built-in Resistor for Current Input
    120 ohms


  • Digital Input

    Sensor Type
    Wet Contact (NPN or PNP) and Dry Contact

    I/O Mode
    DI or event counter

    Dry Contact
    • On: short to GND
    • Off: Open

    Wet Contact (DI to GND)
    • On: 0 to 3 VDC
    • Off: 10 to 30 VDC

    Common Type
    6 points per COM

    Isolation
    3k VDC or 2k Vrms

    Counter Frequency
    900 Hz

    Digital Filtering Time Interval
    Software selectable


  • Digital Output

    Type
    Sink

    I/O Mode
    DO or Pulse Output

    Pulse Output Frequency
    1 kHz

    Over-voltage Protection
    45 VDC

    Over-current Protection
    2.6 A (4 channels @ 650 mA)

    Over-temperature Shutdown
    175°C (min.)

    Current Rating
    200 mA per channel

    Isolation
    3k VDC or 2k Vrms


  • Power Requirements

    Power Consumption
    178 mA @ 24 VDC


  • MTBF (mean time between failures)

    Time
    204,391 hrs

    Database
    Telcordia (Bellcore)



    Common Specifications


  • LAN

    Ethernet
    1 10/100 Mbps RJ45 port

    Protection
    1.5 kV magnetic isolation

    Protocols
    Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP


  • Serial Communication

    Interface
    RS-485-2w: Data+, Data-, GND (3-contact terminal block)

    Serial Line Protection
    15 kV ESD for all signals


  • Serial Communication Parameters

    Parity
    None

    Data Bits
    8

    Stop Bits
    1

    Flow Control
    None

    Baudrate
    1200 to 115200 bps

    Protocol
    Modbus/RTU


  • Power Requirements

    Power Input
    24 VDC nominal, 12 to 36 VDC


  • Physical Characteristics

    Wiring
    I/O cable max. 14 AWG

    Dimensions
    115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)

    Weight
    under 250 g

    Mounting
    DIN rail or wall


  • Environmental Limits

    Operating Temperature
    Standard Models: -10 to 60°C (14 to 140°F)
    Wide Temp. Models: -40 to 75°C (-40 to 167°F)

    Storage Temperature
    -40 to 85°C (-40 to 185°F)

    Ambient Relative Humidity
    5 to 95% (non-condensing)

    Altitude
    Up to 2000 m

    Note Please contact us if you require products guaranteed to function properly at higher altitudes.


  • Standards and Certifications

    Safety
    UL 508

    EMI
    EN 61000-3-2; EN 61000-3-3; EN 61000-6-4;

    FCC
    Part 15, Subpart B, Class A

    EMS
    EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
    EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2

    Shock
    IEC 60068-2-27

    Freefall
    IEC 60068-2-32

    Vibration
    IEC 60068-2-6

    Green Product
    RoHS, CRoHS, WEEE



  • Ordering Information

    Available Modules
    ioLogik E2242 Ethernet Micro RTU Controller with 4 analog inputs and 12 configurable DIOs,
    -10 to 60°C operating temperature
    ioLogik E2242-T Ethernet Micro RTU Controller with 4 analog inputs and 12 configurable DIOs,
    -40 to 75°C operating temperature